Alde Furnace: “Overheat (red fail)”
danger RV furnace fault codes
What it means
The overheat protection on the red cable has tripped. The boiler reached an over-temperature condition, commonly because it ran at high power while air pockets in the glycol heating loop prevented proper heat transfer.
Most likely causes
- Air pockets in the heating system, especially when running at high power most likely
- Low fluid level in the expansion tank common
- Circulation pump not running or not circulating fluid common
Safe checks you can do yourself
- Bleed/vent the heating system of air using the air vents located around the system
- Check the fluid level in the expansion tank: it should sit about 1 cm above the Min mark when cool
- Confirm the circulation pump is responding and moving fluid
- Allow about 15 minutes for the fluid to cool before restarting
How to reset / clear Overheat (red fail)
- Let the system cool for roughly 15 minutes and correct the air/fluid/pump issue
- Reset: disconnect the panel from the boiler, remove 230V, and disconnect 12V from the boiler
- Reconnect and restart; if the fault returns, contact a dealer
When to call a technician
If the overheat fault recurs after bleeding the system, topping up fluid and confirming the pump runs, contact an Alde dealer.
Applies to
Alde Compact 3020 HE
FAQ
What does Alde Furnace code "Overheat (red fail)" mean?
The overheat protection on the red cable has tripped. The boiler reached an over-temperature condition, commonly because it ran at high power while air pockets in the glycol heating loop prevented proper heat transfer.
How do I reset Alde Furnace Overheat (red fail)?
Let the system cool for roughly 15 minutes and correct the air/fluid/pump issue Reset: disconnect the panel from the boiler, remove 230V, and disconnect 12V from the boiler Reconnect and restart; if the fault returns, contact a dealer
What is the most common cause of Overheat (red fail) on a Alde Furnace?
The most likely cause is air pockets in the heating system, especially when running at high power.
Related · Alde furnace
The boiler tried to ignite the LPG burner but did not establ… Low battery
The 12V supply to the boiler has dropped below about 10.5V, … Overheat PCB
The boiler's circuit board (PCB) failsafe over-temperature p…
Sources
- Operating Instructions – Alde Compact 3020 HE — Section 9:1 Error Messages – Overheat red fail; Section 10 Resetting (Alde International)
Note: A related Overheat blue fail message exists for the blue-cable overheat sensor; the manual lists it without separate detailed steps.
● Last verified 2026-06-29 · compiled from manufacturer documentation. Codes can vary by model year — always cross-check your unit’s manual.